Title: An adaptive approach to load shedding and spinning reserve control during underfrequency conditions

Abstract

Emergency conditions arising due to generating power deficiency and the consequent drop in power system frequency can lead to system collapse and a large scale loss of load. Underfrequency load shedding (UFLS) is a globally accepted practice to handle this situation. Most UFLS schemes use pre-specified step sizes based upon frequency measurements. This paper presents an adaptive scheme which uses both frequency and rate-of-change of frequency measurements to dynamically set UFLS relays if more than one generation outage is experienced. It then proposes a technique for coordinating UFLS and the activation of spinning reserves through localized governor control. Recent developments in computer based frequency and rate-of-change of frequency relays makes this scheme both feasible and attractive.

Authors:
;  [1]; ;  [2]
  1. Riga Technical Univ. (Latvia)
  2. Univ. of Washington, Seattle, WA (United States). Dept. of Electrical Engineering
Publication Date:
OSTI Identifier:
435369
Report Number(s):
CONF-960111-
Journal ID: ITPSEG; ISSN 0885-8950; TRN: IM9710%%27
Resource Type:
Journal Article
Journal Name:
IEEE Transactions on Power Systems
Additional Journal Information:
Journal Volume: 11; Journal Issue: 4; Conference: IEEE Power Engineering Society (PES) Winter meeting, Baltimore, MD (United States), 21-25 Jan 1996; Other Information: PBD: Nov 1996
Country of Publication:
United States
Language:
English
Subject:
24 POWER TRANSMISSION AND DISTRIBUTION; POWER SYSTEMS; LOAD MANAGEMENT; STABILIZATION; CAPACITY; FREQUENCY DEPENDENCE

Citation Formats

Chuvychin, V N, Gurov, N S, Venkata, S S, and Brown, R E. An adaptive approach to load shedding and spinning reserve control during underfrequency conditions. United States: N. p., 1996. Web. doi:10.1109/59.544646.
Chuvychin, V N, Gurov, N S, Venkata, S S, & Brown, R E. An adaptive approach to load shedding and spinning reserve control during underfrequency conditions. United States. https://doi.org/10.1109/59.544646
Chuvychin, V N, Gurov, N S, Venkata, S S, and Brown, R E. 1996. "An adaptive approach to load shedding and spinning reserve control during underfrequency conditions". United States. https://doi.org/10.1109/59.544646.
@article{osti_435369,
title = {An adaptive approach to load shedding and spinning reserve control during underfrequency conditions},
author = {Chuvychin, V N and Gurov, N S and Venkata, S S and Brown, R E},
abstractNote = {Emergency conditions arising due to generating power deficiency and the consequent drop in power system frequency can lead to system collapse and a large scale loss of load. Underfrequency load shedding (UFLS) is a globally accepted practice to handle this situation. Most UFLS schemes use pre-specified step sizes based upon frequency measurements. This paper presents an adaptive scheme which uses both frequency and rate-of-change of frequency measurements to dynamically set UFLS relays if more than one generation outage is experienced. It then proposes a technique for coordinating UFLS and the activation of spinning reserves through localized governor control. Recent developments in computer based frequency and rate-of-change of frequency relays makes this scheme both feasible and attractive.},
doi = {10.1109/59.544646},
url = {https://www.osti.gov/biblio/435369}, journal = {IEEE Transactions on Power Systems},
number = 4,
volume = 11,
place = {United States},
year = {1996},
month = {11}
}