skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Above ground detection and interpretation of transient signals on underground power distribution systems

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.368414· OSTI ID:39971
 [1];  [2]
  1. Purdue Univ., W. Lafayette, IN (United States)
  2. Biddle Instruments, Blue Bell, PA (United States)

A relatively simple system for recording any high voltage/current transients that occur on underground power distribution systems is described. Experimental data resulting from faults on two different 15kV class URD systems with helical neutrals is presented. A procedure for and discussion of the interpretation of the data is also presented in some detail. The most obvious application is for immediate fault location but the remarkable reproducibility of the data suggests other applications.

OSTI ID:
39971
Report Number(s):
CONF-9404175-; ISSN 0885-8977; TRN: IM9520%%165
Journal Information:
IEEE Transactions on Power Delivery, Vol. 10, Issue 1; Conference: Institute of Electrical and Electronics Engineers/Power Engineering Society (IEEE/PES) transmission and distribution conference, Chicago, IL (United States), 10-15 Apr 1994; Other Information: PBD: Jan 1995
Country of Publication:
United States
Language:
English