Design and dynamic response characteristics of 400 MW adjustable speed pumped storage unit for Ohkawachi Power Station
Journal Article
·
· IEEE Transactions on Energy Conversion
- Hitachi, Ltd., Tokyo (Japan)
- Kansai Electric Power Co., Inc., Osaka (Japan)
A 400 MW world`s largest adjustable speed pumped storage unit for Ohkawachi Power Station, the Kansai Electric Power Co., Inc., Japan, was commissioned on Dec. 3, 1993. It can change power in steps of at least 32MW in the generate mode and at least 80MW in the pump mode, within 0.2 s. This paper describes principal design considerations for the control systems of the machine and presents actual performance of the machine with reference to some typical oscillograph charts.
- OSTI ID:
- 276823
- Report Number(s):
- CONF-950727-; ISSN 0885-8969; TRN: IM9636%%498
- Journal Information:
- IEEE Transactions on Energy Conversion, Vol. 11, Issue 2; Conference: 1995 IEEE Power Engineering Society summer meeting, Portland, OR (United States), 23-27 Jul 1995; Other Information: PBD: Jun 1996
- Country of Publication:
- United States
- Language:
- English
Similar Records
Development of an optical current transformer for adjustable speed pumped storage systems
Gaining flexibility, value with adjustable-speed hydro
Making the old better with new machines
Journal Article
·
Wed Jan 01 00:00:00 EST 1997
· IEEE Transactions on Power Delivery
·
OSTI ID:276823
+3 more
Gaining flexibility, value with adjustable-speed hydro
Journal Article
·
Sat Dec 31 00:00:00 EST 1994
· Hydro Review Worldwide
·
OSTI ID:276823
Making the old better with new machines
Journal Article
·
Sat Dec 31 00:00:00 EST 1994
· Hydro Review Worldwide
·
OSTI ID:276823