Title: An experimental study of the behavior of a high efficiency residential heat pump in cooling mode with common installation faults imposed

Journal Article · · Applied Thermal Engineering

Faults are believed to be common in split system air-conditioner and heat pump systems, due to operating degradation or installation problems. Common faults include improper refrigerant charge, reduced evaporator airflow, liquid line restrictions, and the presence of non-condensable gas. Laboratory tests were used to quantify fault impacts on performance of a heat pump system, and impacts on indicator variables such as refrigerant temperatures and pressures. This paper describes a large set of laboratory tests implemented on a high efficiency heat pump operating in cooling mode. This system uses R-410A refrigerant and has a rotary compressor, TXV, two accumulators, and a compensator. A small number of previous experimental studies have been done previously to study the effects of some operating faults, but none has examined a modern system with these components. The tests were conducted with a range of fault intensities and driving conditions. The results are compared to previous researchers’ experimental results. The system’s performance was found to be quite robust in the presence of faults. The TXV, accumulators, and compensator significantly reduce sensitivity to refrigerant charge and liquid line restriction faults, and other faults to a lesser extent.

Research Organization:
Univ. of Nebraska, Lincoln, NE (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
Grant/Contract Number:
EE0008689
OSTI ID:
1673774
Alternate ID(s):
OSTI ID: 1780229
Journal Information:
Applied Thermal Engineering, Vol. 184; ISSN 1359-4311
Publisher:
ElsevierCopyright Statement
Country of Publication:
United States
Language:
English

References (21)

Evaluating the Performance of a Fault Detection and Diagnostic System for Vapor Compression Equipment journal October 1998
Common Faults and Their Impacts for Rooftop Air Conditioners journal July 1998
Normalized performance parameters for a residential heat pump in the cooling mode with single faults imposed journal June 2014
Effect of common faults on the performance of different types of vapor compression systems journal April 2016
System performance characteristics of an air conditioner over a range of charging conditions journal November 1991
Effect of refrigerant charge on the performance of air conditioning systems journal January 2001
Accurate Charge Inventory Modeling for Unitary Air Conditioners journal January 2003
The effects of outdoor air-side fouling on frost growth and heat transfer characteristics of a microchannel heat exchanger: An experimental study journal April 2020
Review Article: Methods for Fault Detection, Diagnostics, and Prognostics for Building Systems—A Review, Part I journal January 2005
Performance of a residential heat pump operating in the cooling mode with single faults imposed journal March 2009
Evaluation of the impacts of refrigerant charge on air conditioner and heat pump performance journal November 2012
Generalized effects of refrigerant charge on normalized performance variables of air conditioners and heat pumps journal April 2017
Generalized effects of faults on normalized performance variables of air conditioners and heat pumps journal January 2018
The effect of improper refrigerant charging on the performance of an air conditioner with capillary tube expansion journal January 1990
Measured effect of airflow and refrigerant charge on the seasonal performance of an air-source heat pump using R-410A journal July 2011
The impact of fouling on the condenser of a vapor compression refrigeration system: An experimental observation journal February 2014
An experimental analysis of the effect of refrigerant charge level and outdoor condition on a window air conditioner journal January 2010
A Statistical, Rule-Based Fault Detection and Diagnostic Method for Vapor Compression Air Conditioners journal January 1997
A Method for Tuning Refrigerant Charge in Modeling Off-Design Performance of Unitary Equipment (RP-1173) journal July 2006
Improved methodologies for simulating unitary air conditioners at off-design conditions journal November 2009
Residential heat pump heating performance with single faults imposed journal April 2011