Title: Impedance-Based Stability Analysis in Grid Interconnection Impact Study Owing to the Increased Adoption of Converter-Interfaced Generators

Abstract

This study investigates the emerging harmonic stability concerns to be addressed by grid planners in generation interconnection studies, owing to the increased adoption of renewable energy resources connected to the grid via power electronic converters. The wideband and high-frequency electromagnetic transient (EMT) characteristics of these converter-interfaced generators (CIGs) and their interaction with the grid impedance are not accurately captured in the typical dynamic studies conducted by grid planners. This paper thus identifies the desired components to be studied and subsequently develops a practical process for integrating a new CIG into a grid with the existing CIGs. The steps of this process are as follows: the impedance equation of a CIG using its control dynamics and an interface filter to the grid, for example, an LCL filter (inductor-capacitor-inductor type), is developed; an equivalent impedance model including the existing CIGs nearby and the grid observed from the point of common coupling are derived; the system stability for credible operating scenarios is assessed. Detailed EMT simulations validate the accuracy of the impedance models and stability assessment for various connection scenarios. Here, by complementing the conventional EMT simulation studies, the proposed analytical approach enables grid planners to identify critical design parameters for seamlessly integratingmore » a new CIG and ensuring the reliability of the grid.« less

Authors:
 [1];  [1];  [2]; ORCiD logo [3]
  1. Yonsei Univ., Seoul (Korea)
  2. Chonbuk National Univ., Jeonju (Korea)
  3. National Renewable Energy Lab. (NREL), Golden, CO (United States)
Publication Date:
Research Org.:
National Renewable Energy Lab. (NREL), Golden, CO (United States)
Sponsoring Org.:
USDOE Office of Energy Efficiency and Renewable Energy (EERE)
OSTI Identifier:
1399078
Report Number(s):
NREL/JA-5D00-70257
Journal ID: ISSN 1996-1073; ENERGA
Grant/Contract Number:
AC36-08GO28308
Resource Type:
Journal Article: Accepted Manuscript
Journal Name:
Energies (Basel)
Additional Journal Information:
Journal Name: Energies (Basel); Journal Volume: 10; Journal Issue: 9; Journal ID: ISSN 1996-1073
Publisher:
MDPI AG
Country of Publication:
United States
Language:
English
Subject:
24 POWER TRANSMISSION AND DISTRIBUTION; impedance-based stability; generator interconnection; converter-interfaced generation; harmonic stability

Citation Formats

Cho, Youngho, Hur, Kyeon, Kang, Yong, and Muljadi, Eduard. Impedance-Based Stability Analysis in Grid Interconnection Impact Study Owing to the Increased Adoption of Converter-Interfaced Generators. United States: N. p., 2017. Web. doi:10.3390/en10091355.
Cho, Youngho, Hur, Kyeon, Kang, Yong, & Muljadi, Eduard. Impedance-Based Stability Analysis in Grid Interconnection Impact Study Owing to the Increased Adoption of Converter-Interfaced Generators. United States. doi:10.3390/en10091355.
Cho, Youngho, Hur, Kyeon, Kang, Yong, and Muljadi, Eduard. Fri . "Impedance-Based Stability Analysis in Grid Interconnection Impact Study Owing to the Increased Adoption of Converter-Interfaced Generators". United States. doi:10.3390/en10091355. https://www.osti.gov/servlets/purl/1399078.
@article{osti_1399078,
title = {Impedance-Based Stability Analysis in Grid Interconnection Impact Study Owing to the Increased Adoption of Converter-Interfaced Generators},
author = {Cho, Youngho and Hur, Kyeon and Kang, Yong and Muljadi, Eduard},
abstractNote = {This study investigates the emerging harmonic stability concerns to be addressed by grid planners in generation interconnection studies, owing to the increased adoption of renewable energy resources connected to the grid via power electronic converters. The wideband and high-frequency electromagnetic transient (EMT) characteristics of these converter-interfaced generators (CIGs) and their interaction with the grid impedance are not accurately captured in the typical dynamic studies conducted by grid planners. This paper thus identifies the desired components to be studied and subsequently develops a practical process for integrating a new CIG into a grid with the existing CIGs. The steps of this process are as follows: the impedance equation of a CIG using its control dynamics and an interface filter to the grid, for example, an LCL filter (inductor-capacitor-inductor type), is developed; an equivalent impedance model including the existing CIGs nearby and the grid observed from the point of common coupling are derived; the system stability for credible operating scenarios is assessed. Detailed EMT simulations validate the accuracy of the impedance models and stability assessment for various connection scenarios. Here, by complementing the conventional EMT simulation studies, the proposed analytical approach enables grid planners to identify critical design parameters for seamlessly integrating a new CIG and ensuring the reliability of the grid.},
doi = {10.3390/en10091355},
journal = {Energies (Basel)},
number = 9,
volume = 10,
place = {United States},
year = {Fri Sep 08 00:00:00 EDT 2017},
month = {Fri Sep 08 00:00:00 EDT 2017}
}

Journal Article: