Experimental Evaluation of Load Rejection Over-Voltage from Grid-Tied Solar Inverters
This paper investigates the impact of load rejection over-voltage (LRO) from commercially available grid-tied photovoltaic (PV) solar inverters. LRO can occur when a local feeder or breaker opens and the power output from a distributed energy resource exceeds the load power. Simplified models of current controlled inverters can over-predict over-voltage magnitudes, thus it is useful to quantify testing. The load rejection event was replicated using a hardware testbed at the National Renewable Energy Laboratory (NREL), and a set of commercially available PV inverters was tested to quantify the impact of LRO for a range of generation-to-load ratios. The magnitude and duration of the over-voltage events are reported in this paper along with a discussion of characteristic inverter output behavior. The results for the inverters under test showed that maximum over-voltage magnitudes were less than 200 percent of nominal voltage, and much lower in many test cases. These research results are important because utilities that interconnect inverter-based DER need to understand their characteristics under abnormal grid conditions.
- Research Organization:
- National Renewable Energy Lab. (NREL), Golden, CO (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE), Renewable Power Office. Solar Energy Technologies Office
- DOE Contract Number:
- AC36-08GO28308
- OSTI ID:
- 1357416
- Report Number(s):
- NREL/PR-5D00-64511
- Resource Relation:
- Conference: Presented at the 42nd IEEE Photovoltaic Specialists Conference (PVSC-42), 14-19 June 2015, New Orleans, Louisiana
- Country of Publication:
- United States
- Language:
- English
Similar Records
Inverter Load Rejection Over-Voltage Testing: SolarCity CRADA Task 1a Final Report
Experimental Evaluation of Grid Support Enabled PV Inverter Response to Abnormal Grid Conditions