Title: Effect of operating conditions on the performance of two-bed closed-cycle solid-sorption heat pump systems

Journal Article · · Journal of Solar Energy Engineering
DOI:https://doi.org/10.1115/1.2847770· OSTI ID:118740
;  [1];  [2]
  1. Univ. of Illinois, Chicago, IL (United States). Dept. of Mechanical Engineering
  2. Gas Research Inst., Chicago, IL (United States)

The effect of two operating parameters, the regeneration temperature and the ambient temperature, on the performance of two-bed, closed-cycle solid-sorption heat pumps is investigated. The results show that increasing the regeneration temperature can improve both the COP and cooling capacity, and the effect on cooling capacity is more significant than the COP. Increasing the regeneration temperature from 180 C to 260 C, the cooling capacity increases by 50% and the COP improves 20%. When the ambient temperature drops, the system performance increases significantly. When the ambient temperature decreases by 10 C from the design point of 35 C, the COP and cooling capacity increases by 50% and 40%, respectively. Also, the bed cycling speed should be increased to achieve the optimum system performance when the regeneration temperature is higher or the ambient temperature becomes lower.