skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Using Whole-Building Electric Load Data in Continuous or Retro-Commissioning

Abstract

Whole-building electric load data can often reveal problems with building equipment or operations. In this paper, we present methods for analyzing 15-minute-interval electric load data. These methods allow building operators, energy managers, and commissioning agents to better understand a building's electricity consumption over time and to compare it to other buildings, helping them to 'ask the right questions' to discover opportunities for electricity waste elimination, energy efficiency, peak load management, and demand response. For example: Does the building use too much energy at night, or on hot days, or in the early evening? Knowing the answer to questions like these can help with retro-commissioning or continuous commissioning. The methods discussed here can also be used to assess how building energy performance varies with time. Comparing electric load before and after fixing equipment or changing operations can help verify that the fixes have the intended effect on energy consumption. Analysis methods discussed in this paper include: ways to graphically represent electric load data; the definition of various parameters that characterize facility electricity loads; and a regression-based electricity load model that accounts for both time of week and outdoor air temperature. The methods are illustrated by applying them to data from commercialmore » buildings. We demonstrate the ability to recognize changes in building operation, and to quantify changes in energy performance. Some key findings are: 1) Plotting time series electric load data is useful for understanding electricity consumption patterns and changes to those patterns, but results may be misleading if data from different time intervals are not weather-normalized. 2) Parameter plots can highlight key features of electric load data and may be easier to interpret than plots of time series data themselves. 3) A time-of-week indicator variable (as compared to time-of-day and day-of-week indicator variables) improves the accuracy of regression models of electric load. 4) A piecewise linear and continuous outdoor air temperature dependence can be derived without the use of a change-point model (which would add complexity to the modeling algorithm) or assumptions about when structural changes occur (which could introduce inaccuracy). 5) A model that includes time-of-week and temperature dependence can be used for weather normalization and can determine whether the building is unusually temperature-sensitive, which can indicate problems with HVAC operation.« less

Authors:
; ; ;
Publication Date:
Research Org.:
Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
Sponsoring Org.:
Environmental Energy Technologies Division
OSTI Identifier:
1051038
Report Number(s):
LBNL-5057E
TRN: US201218%%1190
DOE Contract Number:  
DE-AC02-05CH11231
Resource Type:
Conference
Resource Relation:
Conference: 19th National Conference on Building Commissioning, Cincinnati, OH, August 10-12, 2011
Country of Publication:
United States
Language:
English
Subject:
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; ACCURACY; AIR; COMMERCIAL BUILDINGS; COMMISSIONING; ELECTRICITY; ENERGY CONSUMPTION; ENERGY EFFICIENCY; MANAGEMENT; OUTDOORS; PEAK LOAD; PERFORMANCE; SIMULATION; TEMPERATURE DEPENDENCE; WASTES; WEATHER

Citation Formats

Price, Phillip N, Mathieu, Johanna L, Kiliccote, Sila, and Piette, Mary Ann. Using Whole-Building Electric Load Data in Continuous or Retro-Commissioning. United States: N. p., 2011. Web.
Price, Phillip N, Mathieu, Johanna L, Kiliccote, Sila, & Piette, Mary Ann. Using Whole-Building Electric Load Data in Continuous or Retro-Commissioning. United States.
Price, Phillip N, Mathieu, Johanna L, Kiliccote, Sila, and Piette, Mary Ann. 2011. "Using Whole-Building Electric Load Data in Continuous or Retro-Commissioning". United States. https://www.osti.gov/servlets/purl/1051038.
@article{osti_1051038,
title = {Using Whole-Building Electric Load Data in Continuous or Retro-Commissioning},
author = {Price, Phillip N and Mathieu, Johanna L and Kiliccote, Sila and Piette, Mary Ann},
abstractNote = {Whole-building electric load data can often reveal problems with building equipment or operations. In this paper, we present methods for analyzing 15-minute-interval electric load data. These methods allow building operators, energy managers, and commissioning agents to better understand a building's electricity consumption over time and to compare it to other buildings, helping them to 'ask the right questions' to discover opportunities for electricity waste elimination, energy efficiency, peak load management, and demand response. For example: Does the building use too much energy at night, or on hot days, or in the early evening? Knowing the answer to questions like these can help with retro-commissioning or continuous commissioning. The methods discussed here can also be used to assess how building energy performance varies with time. Comparing electric load before and after fixing equipment or changing operations can help verify that the fixes have the intended effect on energy consumption. Analysis methods discussed in this paper include: ways to graphically represent electric load data; the definition of various parameters that characterize facility electricity loads; and a regression-based electricity load model that accounts for both time of week and outdoor air temperature. The methods are illustrated by applying them to data from commercial buildings. We demonstrate the ability to recognize changes in building operation, and to quantify changes in energy performance. Some key findings are: 1) Plotting time series electric load data is useful for understanding electricity consumption patterns and changes to those patterns, but results may be misleading if data from different time intervals are not weather-normalized. 2) Parameter plots can highlight key features of electric load data and may be easier to interpret than plots of time series data themselves. 3) A time-of-week indicator variable (as compared to time-of-day and day-of-week indicator variables) improves the accuracy of regression models of electric load. 4) A piecewise linear and continuous outdoor air temperature dependence can be derived without the use of a change-point model (which would add complexity to the modeling algorithm) or assumptions about when structural changes occur (which could introduce inaccuracy). 5) A model that includes time-of-week and temperature dependence can be used for weather normalization and can determine whether the building is unusually temperature-sensitive, which can indicate problems with HVAC operation.},
doi = {},
url = {https://www.osti.gov/biblio/1051038}, journal = {},
number = ,
volume = ,
place = {United States},
year = {Fri Jul 01 00:00:00 EDT 2011},
month = {Fri Jul 01 00:00:00 EDT 2011}
}

Conference:
Other availability
Please see Document Availability for additional information on obtaining the full-text document. Library patrons may search WorldCat to identify libraries that hold this conference proceeding.

Save / Share: