dc arc interruption in pressurized gasses
The purpose of the study was to investigate the possibility of achieving (1) short interruption time and (2) minimum contact erosion in a dc circuit interrupter. Arc interruption tests were performed on a 100-A, 600-V dc contactor under atmospheres of argon dry air, nitrogen, helium and hydrogen, each at four pressures 0.17, 0.34, 0.52, and 0.69 MPa (25, 50, 75 and 100 psig). It was found that the average arcing time in helium and hydrogen was the shortest, and that in argon the longest for the circuit conditions used. The contact erosion in hydrogen was the worst, and that in argon the best for the contact materials used in the tests. The static pressure in the chamber did not appear to have much effect on the arc interruption phenomenon for the contactor and gas pressures used.
- Research Organization:
- Los Alamos National Laboratory (LANL), Los Alamos, NM (United States)
- DOE Contract Number:
- W-7405-ENG-36
- OSTI ID:
- 6749022
- Report Number(s):
- LA-UR-80-2344; CONF-810201-1
- Resource Relation:
- Conference: IEEE Power Engineering Society meeting, Atlanta, GA, USA, Feb 1981
- Country of Publication:
- United States
- Language:
- English
Similar Records
Development of a dc current limiting interrupting system for mines. Open file report Jun 79-Sep 81
Switch contact device for interrupting high current, high voltage, AC and DC circuits
Related Subjects
CIRCUIT BREAKERS
PERFORMANCE
EHV DC SYSTEMS
AIR
ARGON
ELECTRIC ARCS
EXPERIMENTAL DATA
HELIUM
HYDROGEN
NITROGEN
CURRENTS
DATA
DC SYSTEMS
ELECTRIC CURRENTS
ELECTRIC DISCHARGES
ELECTRICAL EQUIPMENT
ELEMENTS
EQUIPMENT
EQUIPMENT PROTECTION DEVICES
FLUIDS
GASES
INFORMATION
NONMETALS
NUMERICAL DATA
POWER SYSTEMS
RARE GASES
200302* - Power Transmission & Distribution- DC Systems- (1989-)