Title: A field demonstration of automatic restroom ventilation control to reduce energy consumption

Technical Report ·
DOI:https://doi.org/10.2172/5675383· OSTI ID:5675383

This report documents the motion sensor evaluation task for the Hanford Energy Management Committee (HEMC) performed by Pacific Northwest Laboratory (PNL) to support the energy reduction mission. The study included installing automatic exhaust ventilation controls in the restrooms of the 1103 Building, 100N area. The goal of this task was to measure the benefit of automatically controlling exhaust ventilation in restrooms of an office building on the Hanford Site. The HEMC belief is that the value of controlling the fans is not limited to the power consumed by the fans, but also includes the value invested to condition (heat or cool) the makeup air. The air exhausted to the exterior of the building must ultimately be replaced by unconditioned air from the outside. This outside air must then by conditioned to maintain the comfort of building occupants. 6 figs., 1 tab.