skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Quantification of the association of ventilation rates with sick building syndrome symptoms

Technical Report ·
DOI:https://doi.org/10.2172/962711· OSTI ID:962711

Data from published studies were combined and analyzed to develop best-fit equations and curves quantifying the change in sick building syndrome (SBS) symptom prevalence with ventilation rate. For each study, slopes were calculated, representing the fractional change in SBS symptom prevalence per unit change in ventilation rate per person. Values of ventilation rate, associated with each value of slope, were also calculated. Linear regression equations were fit to the resulting data points, after weighting by study size. Integration of the slope-ventilation rate equations yielded curves of relative SBS symptom prevalence versus ventilation rate. Based on these analyses, relative SBS symptom prevalence increases approximately 23percent (12percent to 32percent) as the ventilation rate drops from 10 to 5 L/s-person and relative prevalence decreases approximately 29percent (15percent to 42percent) as ventilation rate increases from 10 to 25 L/s-person.

Research Organization:
Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
Sponsoring Organization:
Environmental Energy Technologies Division
DOE Contract Number:
DE-AC02-05CH11231
OSTI ID:
962711
Report Number(s):
LBNL-2035E; TRN: US200917%%92
Country of Publication:
United States
Language:
English