Title: Calculation code evaluating the confinement of a nuclear facility in case of fires

Technical Report ·
DOI:https://doi.org/10.2172/95670· OSTI ID:95670

Accident events involving fire are quite frequent and could have a severe effect on the safety of nuclear facilities. As confinement must be maintained, the ventilation and filtration systems have to be designed to limit radioactive release to the environment. To determine and analyse the consequences of a fire on the contamination confinement, IPSN, COGEMA and SGN are participating in development of a calculation code based on introduction, in the SIMEVENT ventilation code, of various models associated to fire risk and mass transfer in the ventilation networks. This calculation code results from the coupling of the SIMEVENT code with several models describing the temperature in a room resulting of a fire, the temperatures along the ventilation ducts, the contamination transfers through out the ventilation equipments (ducts, dampers, valves, air cleaning systems) and the High Efficiency Particulate Air (HEPA) filters clogging. The paper proposed presents the current level of progress in development of this calculation code. It describes, in particular, the empirical model used for the clogging of HEPA filters by the aerosols derived from the combustion of standard materials used in the nuclear industry. It describes, also, the specific models used to take into account the mass transfers and resulting from the basic mechanisms of aerosols physics. In addition, an assessment of this code is given using the example of a simple laboratory installation.

Research Organization:
USDOE Assistant Secretary for Environment, Safety, and Health, Washington, DC (United States). Office of Environmental Guidance; US Nuclear Regulatory Commission (NRC), Washington, DC (United States). Office of Nuclear Regulatory Research; International Society of Nuclear Air Treatment Technologies, Inc., Batavia, OH (United States); Harvard Univ., Boston, MA (United States). Harvard Air Cleaning Lab.
OSTI ID:
95670
Report Number(s):
NUREG/CP-0141; CONF-940738-; ON: TI95007828; TRN: 95:018833
Resource Relation:
Conference: 23. DOE/NRC nuclear air cleaning and treatment conference, Buffalo, NY (United States), 25-28 Jul 1994; Other Information: PBD: Feb 1995; Related Information: Is Part Of Proceedings of the 23rd DOE/NRC nuclear air cleaning conference; First, M.W. [ed.] [Harvard Univ., Boston, MA (United States). Harvard Air Cleaning Lab.]; PB: 820 p.
Country of Publication:
United States
Language:
English

Similar Records

Analysis and consequences of fire inside the ventilation ducts of a nuclear facility
Conference · Sun Jan 01 00:00:00 EST 1989 · ASHRAE Transactions (American Society of Heating, Refrigerating and Air-Conditioning Engineers); (USA) · OSTI ID:95670

Fire-accident analysis code (FIRAC) verification
Conference · Wed Jan 01 00:00:00 EST 1986 · OSTI ID:95670

Tracking Radioactive Isotopes in HVAC and Application for Hot Cell Analyses - 20155
Conference · Wed Jul 01 00:00:00 EDT 2020 · OSTI ID:95670