Originally the PEP-II injection kickers were powered by one power supply. Since the kicker magnets where not perfectly matched, the stored beam got excited by about 7% of the maximum kicker amplitude. This led to luminosity losses which were especially obvious for trickle injection when the detector is on for data taking. Therefore two independent power supplies with thyratrons in the tunnel next to the kicker magnet were installed. This also reduces the necessary power by about a factor of four since there are no long cables that have to be charged. The kickers are now independently adjustable to eliminate any non-closure of the kicker system and therefore excitation of the stored beam. Setup, commissioning and fine tuning of this system are discussed.

Research Organization:
SLAC National Accelerator Lab., Menlo Park, CA (United States)
Sponsoring Organization:
USDOE
DOE Contract Number:
AC02-76SF00515
OSTI ID:
890813
Report Number(s):
SLAC-PUB-11232; TRN: US0604809
Resource Relation:
Conference: Contributed to Particle Accelerator Conference (PAC 05), Knoxville, Tennessee, 16-20 May 2005