Condensation in the exhaust gas system of an incinerator burning low activity radioactive wastes led to numerous corrosion developments and rapid failure of the discharge filters. The problem was traced to insufficient reheat of the exhaust gases following scrubbing. Rust particulate and moisture loaded the filters, leading to water accumulation, chloride cracking of the filter housings, and plugging and tearing of the filter media itself. To mitigate the problem, the exhaust gas temperature was increased, thermal insulation was installed on the ductwork, and the interiors of the ducts and new filter housings were lined with a protective coating.
- Research Organization:
- Savannah River Site (SRS), Aiken, SC (United States)
- Sponsoring Organization:
- US Department of Energy (US)
- DOE Contract Number:
- AC09-96SR18500
- OSTI ID:
- 817860
- Report Number(s):
- WSRC-MS-2002-00493; TRN: US0305225
- Resource Relation:
- Conference: NACE/Corrosion, New Orleans, LA (US), 03/28/2004--04/01/2004; Other Information: PBD: 31 Oct 2003
- Country of Publication:
- United States
- Language:
- English
Similar Records
INCINERATOR AND OFF-GAS SCRUBBER TESTS
Diesel engine exhaust trap particulate distribution and incineration balancing system
Investigation of water accumulation in an offgas test facility HEPA housing
Technical Report
·
Wed Mar 01 00:00:00 EST 1961
·
OSTI ID:817860
Diesel engine exhaust trap particulate distribution and incineration balancing system
Patent
·
Tue Sep 22 00:00:00 EDT 1981
·
OSTI ID:817860
Investigation of water accumulation in an offgas test facility HEPA housing
Conference
·
Sun Jun 01 00:00:00 EDT 1997
·
OSTI ID:817860
+1 more