Properties and Cycle Performance of Refrigerant Blends Operating Near and Above the Refrigerant Critical Point, Task 2: Air Conditioner System Study
The main goal of this project was to investigate and compare the performance of an R410A air conditioner to that of an R22 air conditioner, with specific interest in performance at high ambient temperatures at which the condenser of the R410A system may be operating above the refrigerant's critical point. Part 1 of this project consisted of conducting comprehensive measurements of thermophysical for refrigerant R125 and refrigerant blends R410A and R507A and developing new equation of state formulations and mixture models for predicting thermophysical properties of HFC refrigerant blends. Part 2 of this project conducted performance measurements of split-system, 3-ton R22 and R410A residential air conditioners in the 80 to 135 F (27.8 to 57.2 C) outdoor temperature range and development of a system performance model. The performance data was used in preparing a beta version of EVAP-COND, a windows-based simulation package for predicting performance of finned-tube evaporators and condensers. The modeling portion of this project also included the formulation of a model for an air-conditioner equipped with a thermal expansion valve (TXV). Capacity and energy efficiency ratio (EER) were measured and compared. The R22 system's performance was measured over the outdoor ambient temperature range of 80 to 135 F (27.8 to 57.2 C). The same test range was planned for the R410A system. However, the compressor's safety system cut off the compressor at the 135.0 F (57.2 C) test temperature. The highest measurement on this system was at 130.0 F (54.4 C). Subsequently, a custom-manufactured R410A compressor with a disabled safety system and a more powerful motor was installed and performance was measured at outdoor temperatures up to 155.0 F (68.3 C). Both systems had similar capacity and EER performance at 82.0 F (27.8 C). The capacity and EER degradation of both systems were nearly linearly dependent with rising ambient outdoor ambient test temperatures. The performance degradation of R410A at higher temperatures was greater than R22. However, the R22 and R410A systems both operated normally during all tests. Visual observations of the R410A system provided no indication of vibrations or TXV hunting at high ambient outdoor test conditions with the compressor operating in the transcritical regime.
- Research Organization:
- Air-Conditioning and Refrigeration Technology Institute (US)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EE) (US)
- DOE Contract Number:
- FC05-99OR22674
- OSTI ID:
- 808637
- Report Number(s):
- DOE/OR22674/605-50010-01-Pt2; ARTI-21CR/605-50010-01-Pt2; TRN: US200308%%86
- Resource Relation:
- Other Information: PBD: 31 Oct 2002
- Country of Publication:
- United States
- Language:
- English
Similar Records
Energy and Economics Analyses of Condenser Evaporative Precooling for Various Climates, Buildings and Refrigerants
Performance of HCFC22 alternative refrigerants
Related Subjects
54 ENVIRONMENTAL SCIENCES
AIR CONDITIONERS
AMBIENT TEMPERATURE
CAPACITY
COMPRESSORS
ENERGY EFFICIENCY
EVAPORATORS
MIXTURES
MOTORS
PERFORMANCE
REFRIGERANTS
SAFETY
SIMULATION
THERMAL EXPANSION
VALVES
REFRIGERANT
AIR CONDITIONER
EER
R22
R-22
R410A
R-410A
TRANSCRITICAL
EVAP-COND