Title: SENSITIVITY OF THE HOUSE PRESSURE TEST FOR DUCT LEAKAGE TO VARIATIONS IN THE DISTRIBUTION OF AIR LEAKAGE IN THE HOUSE ENVELOPE

Technical Report ·
DOI:https://doi.org/10.2172/758983· OSTI ID:758983

The house pressure test for air leakage in ducts calculates the signed difference between the supply and return leakage from the response of the air pressure in the house to operation of the system fan. The currently accepted version of this calculation was based on particular assumptions about how the house envelope leakage is distributed between the walls, ceiling, and floor. This report generalizes the equation to account for an arbitrary distribution of envelope leakage. It concludes that the currently accepted equation is usually accurate to within {+-}5%, but in a small proportion of cases the results may diverge by 50% or more.