45-Day safety screen results for Tank 241-BY-103, auger samples 95-AUG-012 and 95-AUG-013
Two auger samples from tank 241-BY-103 (BY-103) were received by the 222-S Laboratories and underwent safety screening analysis, consisting of differential scanning calorimetry (DSC), thermogravimetric analysis (TGA), and total alpha activity. Analytical results for the TGA analyses for both samples were less than the safety screening notification limit. Since notification is made if the sample is analyzed at less than 17% water, notification was made on April 20, 1995. Although the sample results were below this limit, no secondary analyses were required or performed. Included in this report are the primary safety screening results obtained from the analyses and copies of all DSC and TGA raw data scans as requested per the TCP. Photographs of the auger samples were taken during extrusion and, although not included in this report, are available. Tank BY-103 is on the ferrocyanide Watch List.
- Research Organization:
- Westinghouse Hanford Co., Richland, WA (United States)
- Sponsoring Organization:
- USDOE, Washington, DC (United States)
- DOE Contract Number:
- AC06-87RL10930
- OSTI ID:
- 71283
- Report Number(s):
- WHC-SD-WM-DP-104; ON: DE95011448; TRN: 95:015304
- Resource Relation:
- Other Information: PBD: 21 Apr 1995
- Country of Publication:
- United States
- Language:
- English