Evaluation of coverage of enriched UF{sub 6} cylinder storage lots by existing criticality accident alarms
The Portsmouth Gaseous Diffusion Plant (PORTS) is leased from the US Department of Energy (DOE) by the United States Enrichment Corporation (USEC), a government corporation formed in 1993. PORTS is in transition from regulation by DOE to regulation by the Nuclear Regulatory Commission (NRC). One regulation is 10 CFR Part 76.89, which requires that criticality alarm systems be provided for the site. PORTS originally installed criticality accident alarm systems in all building for which nuclear criticality accidents were credible. Currently, however, alarm systems are not installed in the enriched uranium hexafluoride (UF{sub 6}) cylinder storage lots. This report analyzes and documents the extent to which enriched UF{sub 6} cylinder storage lots at PORTS are covered by criticality detectors and alarms currently installed in adjacent buildings. Monte Carlo calculations are performed on simplified models of the cylinder storage lots and adjacent buildings. The storage lots modelled are X-745B, X-745C, X745D, X-745E, and X-745F. The criticality detectors modelled are located in building X-343, the building X-344A/X-342A complex, and portions of building X-330. These criticality detectors are those located closest to the cylinder storage lots. Results of this analysis indicate that the existing criticality detectors currently installed at PORTS are largely ineffective in detecting neutron radiation from criticality accidents in most of the cylinder storage lots at PORTS, except sometimes along portions of their peripheries.
- Research Organization:
- Martin Marietta Energy Systems, Inc., Piketon, OH (United States)
- Sponsoring Organization:
- USDOE, Washington, DC (United States)
- DOE Contract Number:
- AC05-76OR00001
- OSTI ID:
- 70812
- Report Number(s):
- POEF-SH-29; ON: DE95010274; TRN: 95:015193
- Resource Relation:
- Other Information: PBD: Mar 1995
- Country of Publication:
- United States
- Language:
- English
Similar Records
Verification of criticality accident alarm system detector locations for the X-326 process cell floor
An examination of criticality accident alarm coverage of the X-710, X-760 Buildings and the north half of the X-7745-R storage pad at the Portsmouth Gaseous Diffusion Plant