Age-related degradation of Westinghouse 480-volt circuit breakers
- Brookhaven National Lab., Upton, NY (USA)
An aging assessment of Westinghouse DS-series low-voltage air circuit breakers was performed as part of the Nuclear Plant Aging Research (NPAR) program. The objectives of this study are to characterize age-related degradation within the breaker assembly and to identify maintenance practices to mitigate their effect. Since this study has been promulgated by the failures of the reactor trip breakers at the McGuire Nuclear Station in July 1987, results relating to the welds in the breaker pole lever welds are also discussed. The design and operation of DS-206 and DS-416 breakers were reviewed. Failure data from various national data bases were analyzed to identify the predominant failure modes, causes, and mechanisms. Additional operating experiences from one nuclear station and two industrial breaker-service companies were obtained to develop aging trends of various subcomponents. The responses of the utilities to the NRC Bulletin 88-01, which discusses the center pole lever welds, were analyzed to assess the final resolution of failures of welds in the reactor trips. Maintenance recommendations, made by the manufacturer to mitigate age-related degradation were reviewed, and recommendations for improving the monitoring of age-related degradation are discussed. As described in Volume 2 of this NUREG, the results from a test program to assess degradation in breaker parts through mechanical cycling are also included. The testing has characterized the cracking of center-pole lever welds, identified monitoring techniques to determine aging in breakers, and provided information to augment existing maintenance programs. Recommendations to improve breaker reliability using effective maintenance, testing, and inspection programs are suggested. 13 refs., 21 figs., 8 tabs.
- Research Organization:
- US Nuclear Regulatory Commission (NRC), Washington, DC (United States). Div. of Engineering; Brookhaven National Lab. (BNL), Upton, NY (United States)
- Sponsoring Organization:
- USNRC
- DOE Contract Number:
- AC02-76CH00016
- OSTI ID:
- 7028755
- Report Number(s):
- NUREG/CR-5280-Vol.1; BNL-NUREG-52178-Vol.1; ON: TI90014174; TRN: 90-028768
- Country of Publication:
- United States
- Language:
- English
Similar Records
Life testing of a low voltage air circuit breaker
Life testing of a low voltage air circuit breaker
Related Subjects
CIRCUIT BREAKERS
AGING
NUCLEAR POWER PLANTS
FAILURES
PERFORMANCE TESTING
REACTOR SAFETY
RECOMMENDATIONS
RELIABILITY
WELDED JOINTS
ELECTRICAL EQUIPMENT
EQUIPMENT
EQUIPMENT PROTECTION DEVICES
JOINTS
NUCLEAR FACILITIES
POWER PLANTS
SAFETY
TESTING
THERMAL POWER PLANTS
220200* - Nuclear Reactor Technology- Components & Accessories
220900 - Nuclear Reactor Technology- Reactor Safety