skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Reliability of the emergency ac-power system at nuclear power plants

Conference ·
OSTI ID:6947723

The reliability of the emergency ac-power systems typical of several nuclear power plants was estimated, the costs of several possible improvements was estimated. Fault trees were constructed based on a detailed design review of the emergency ac-power systems of 18 nuclear plants. The failure probabilities used in the fault trees were calculated from extensive historical data collected from Licensee Event Reports (LERs) and from operating experience information obtained from nuclear plant licensees. It was found that there are not one or two improvements that can be made at all plants to significantly increase the industry-average emergency ac-power-system reliability, but the improvements are varied and plant-specific. Estimates of the improvements in reliability and the associated cost are estimated using plant-specific designs and failure probabilities.

Research Organization:
Oak Ridge National Lab., TN (USA); JBF Associates, Knoxville, TN (USA); Nuclear Regulatory Commission, Rockville, MD (USA)
DOE Contract Number:
W-7405-ENG-26
OSTI ID:
6947723
Report Number(s):
CONF-820802-23-Draft; ON: DE82022336
Resource Relation:
Conference: International meeting on thermal nuclear reactor safety, Chicago, IL, USA, 29 Aug 1982; Other Information: Portions of document are illegible
Country of Publication:
United States
Language:
English