Title: Methodology for evaluation of insulation-debris effects. Containment emergency sump performance-unresolved safety issue A-43

Technical Report ·
DOI:https://doi.org/10.2172/6733320· OSTI ID:6733320

The postulated failure of high energy piping within a light water reactor containment has raised safety questions related to the generation of insulation debris, the migration of such debris to the containment emergency sump screens and the potential for severe screen blockages. High, or total, screen blockages could result in impairment of the long term RHR recirculation systems. Debris considerations are an integral part of the unresolved Safety Issue A-43, Containment Emergency Sump Performance. This report develops calculational methods and debris transport models which can be used for estimating the quantities of debris that might be generated by a LOCA, the transport of such debris, methods for estimating screen blockages and attendant pressure losses. Five operating plants were analyzed using this debris evaluation methodology. These calculations show the dependency on plant containment layout, sump location and design, and types and quantities of insulation employed. 9 figures, 6 tables.

Research Organization:
Burns and Roe, Inc., Woodbury, NY (USA)
DOE Contract Number:
AC04-76DP00789
OSTI ID:
6733320
Report Number(s):
NUREG/CR-2791; SAND-82-7067; ON: DE83001108
Resource Relation:
Other Information: Portions of document are illegible
Country of Publication:
United States
Language:
English