Title: Induction cell breakdown experiments for the Dual-Axis Radiographic Hydrotest (DARHT) Facility

Conference ·

Linear induction cells for the Dual-Axis Radiographic Hydrotest (DARHT) Facility have been tested to determine their high-voltage breakdown characteristics. A variety of full scale insulators were tested both in actual cells and in fixtures simulating induction cells. All insulators were constructed using cross-linked polystyrene (Rexolite). High-voltage pulses up to 550 kV were applied to the insulators using both a 60-ns pulse Blumlein and a 200-ns pulse cable Marx. Two different vacuum gaps were used in these tests, 1.46 and 1.91 cm. The tests were performed at various vacuum levels ranging from 1 {times} 10{sup {minus}6} to 5 {times} 10{sup {minus}8} torr. Breakdown tests of the insulators were also performed with an electron beam generated in the vacuum gap through the use of a velvet emitter. The gap voltage and current were measured using calibrated E-dot and B-dot probes. 15 refs., 7 figs.

Research Organization:
Los Alamos National Laboratory (LANL), Los Alamos, NM (United States)
Sponsoring Organization:
USDOE; USDOE, Washington, DC (USA)
DOE Contract Number:
W-7405-ENG-36
OSTI ID:
5759345
Report Number(s):
LA-UR-91-2051; CONF-910640-20; ON: DE91014603
Resource Relation:
Conference: 8. IEEE pulsed power conference, San Diego, CA (United States), 17-19 Jun 1991
Country of Publication:
United States
Language:
English