Title: Ventilating-air change rate versus particulate contaminant spread

Technical Report ·
DOI:https://doi.org/10.2172/5381349· OSTI ID:5381349

This study provides information on the spread of particulate contamination from glovebox leaks in plutonium manufacturing facilities, with emphasis on the effect of ventilating-air change rate on contaminated spread. A new, very sensitive aerosol tracer technique was developed to simulate plutonium aerosol leaks and its dispersion in a room. The tracer, a submicron aerosol of phloroglucinol, does not interfere with work activity and is detected by its ability to form ice crystals in a supercooled cloud. This technique was applied in Buildings 371 and 707 plutonium production areas. The tracer spread throughout the rooms in a few minutes and reached its equilibrium concentration in 10 to 25 min. Also, to clear the room of all tracer took about the same time. In one room, tracer concentration decreased proportionally to the air change rate, while in the second one, air change rate had no effect. This points out the need for air velocity data. Also, future work must include simultaneous particle concentration measurements at several points. 4 refs., 9 figs., 2 tabs.

Research Organization:
Rockwell International Corp., Golden, CO (United States). Rocky Flats Plant
DOE Contract Number:
AC04-76DP03533
OSTI ID:
5381349
Report Number(s):
RFP-4154; ON: DE88006977
Country of Publication:
United States
Language:
English