HVDC-AC system interaction from AC harmonics. Volume 1. Harmonic impedance calculations. Final report
Improved methods are needed to characterize ac system harmonic behavior for ac filter design for HVDC systems. The purpose of this General Electric Company RP1138 research is to evaluate the present filter design practice and to investigate methods for calculating system harmonic impedances. An overview of ac filter design for HVDC systems and a survey of literature related to filter design have been performed. Two methods for calculating system harmonic impedances have been investigated. In the measurement method, an instrumentation system for measuring system voltage and current has been assembled. Different schemes of using the measurements to calculate system harmonic impedances have been studied. In the analytical method, a procedure to include various operating conditions has been proposed. Computer programs for both methods have been prepared, and the results of the measurement and analytical methods analyzed. A conclusion of the project is that the measurement and analytical methods both provided reasonable results. There are correlations between the measured and analytical results for most harmonics, although there are discrepancies between the assumptions used in the two methods. A sensitivity approach has been proposed to further correlate the results. From the results of the analysis, it is recommended that both methods should be tested further. For the measurement method, more testing should be done to cover different system operating conditions. In the analytical method, more detailed models for representing system components should be studied. In addition, alternative statistical and sensitivity approaches should be attempted.
- Research Organization:
- General Electric Co., Schenectady, NY (USA). Electric Utility Systems Engineering Dept.
- OSTI ID:
- 5092890
- Report Number(s):
- EPRI-EL-2583-Vol.1; ON: DE82021015
- Resource Relation:
- Other Information: Portions of document are illegible
- Country of Publication:
- United States
- Language:
- English
Similar Records
Controlling harmonic instability of HVDC links connected to weak ac systems
Solution to the problem of low order harmonic resonance from HVDC converters
Related Subjects
ELECTRIC FILTERS
NOISE
HVDC SYSTEMS
RECTIFIERS
DESIGN
EXPERIMENTAL DATA
HARMONICS
HVAC SYSTEMS
INTERCONNECTED POWER SYSTEMS
MATHEMATICAL MODELS
MEASURING METHODS
THEORETICAL DATA
AC SYSTEMS
DATA
DC SYSTEMS
ELECTRICAL EQUIPMENT
ENERGY SYSTEMS
EQUIPMENT
FILTERS
INFORMATION
NUMERICAL DATA
OSCILLATIONS
POWER SYSTEMS
200302* - Power Transmission & Distribution- DC Systems- (1989-)