skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: NRC staff review of licensee responses to pressure-locking and thermal-binding issue

Conference ·
OSTI ID:402026

Commercial nuclear power plant operating experience has indicated that pressure locking and thermal binding represent potential common mode failure mechanisms that can cause safety-related power-operated gate valves to fail in the closed position, thus rendering redundant safety-related systems incapable of performing their safety functions. In Generic Letter (GL) 95-07, {open_quotes}Pressure Locking and Thermal Binding of Safety-Related Power-Operated Gate Valves,{close_quotes} the U.S. Nuclear Regulatory Commission (NRC) staff requested that nuclear power plant licensees take certain actions to ensure that valves susceptible to pressure locking or thermal binding are capable of performing their safety functions within the current licensing bases of the facility. The NRC staff has received summary information from licensees in response to GL 95-07 describing actions they have taken to prevent the occurrence of pressure locking and thermal binding. The NRC staff has developed a systematic process to help ensure uniform and consistent review of licensee submittals in response to GL 95-07.

Research Organization:
American Society of Mechanical Engineers (ASME), New York, NY (United States)
OSTI ID:
402026
Report Number(s):
NUREG/CP-0152; CONF-9607103-; ON: TI96013645; TRN: 96:005268-0060
Resource Relation:
Conference: 4. NRC/ASME symposium on valve and pump testing in nuclear power plants, Washington, DC (United States), 15-18 Jul 1996; Other Information: PBD: [1996]; Related Information: Is Part Of Proceedings of the 4th NRC/ASME symposium on valve and pump testing; PB: 719 p.
Country of Publication:
United States
Language:
English