Title: Energy savings in one-pipe steam heating systems fitted with high-capacity air vents. Final report

Technical Report ·
DOI:https://doi.org/10.2172/10191625· OSTI ID:10191625

Multifamily buildings heated by one-pipe steam systems experience significant temperature gradients from apartment to apartment, often reaching 15{degrees}F. As a result, many tenants are to cold, or if the heating system output is increased so as to heat the coldest apartment adequately, too hot. While both are undesirable, the second is particularly so because it wastes energy. It was thought that insufficient air venting of the steam pipes contributed to the gradient. Theoretically, if steam mains and risers are quickly vented, steam will reach each radiator at approximately the same time and balance apartment temperatures. The project`s objective was to determine if the installation of large-capacity air vents at the ends of steam mains and risers would economically reduce the temperature gradient between apartments and reduce the amount of space heating energy required. The test was conducted by enabling and disabling air vents biweekly in 10 multifamily buildings in New York City between December 1992 to May 1993. The temperatures of selected apartments and total space heating energy were compared during each venting regime. There was no difference in energy consumption between ``vents on`` and ``vents off`` periods (see Tables 2 and 5); however, there was a reduction in the maximum spread of apartment temperatures.

Research Organization:
EME Group, New York, NY (United States)
Sponsoring Organization:
New York State Energy Research and Development Authority, Albany, NY (United States)
OSTI ID:
10191625
Report Number(s):
NYSERDA-94-15; ON: DE95001889
Resource Relation:
Other Information: PBD: Sep 1994
Country of Publication:
United States
Language:
English