skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Aging assessment of essential HVAC chillers used in nuclear power plants. Phase 1, Volume 1

Technical Report ·
DOI:https://doi.org/10.2172/10186028· OSTI ID:10186028
;  [1]
  1. Pacific Northwest Lab., Richland, WA (United States)

The Pacific Northwest Laboratory conducted a Phase I aging assessment of chillers used in the essential safety air-conditioning systems of nuclear power plants. Centrifugal chillers in the 75- to 750-ton refrigeration capacity range are the predominant type used. The chillers used, and air-conditioning systems served, vary in design from plant-to-plant. It is crucial to keep chiller internals very clean and to prevent the leakage of water, air, and other contaminants into the refrigerant containment system. Periodic operation on a weekly or monthly basis is necessary to remove moisture and noncondensable gases that gradually build up inside the chiller. This is especially desirable if a chiller is required to operate only as an emergency standby unit. The primary stressors and aging mechanisms that affect chillers include vibration, excessive temperatures and pressures, thermal cycling, chemical attack, and poor quality cooling water. Aging is accelerated by moisture, non-condensable gases (e.g., air), dirt, and other contamination within the refrigerant containment system, excessive start/stop cycling, and operating below the rated capacity. Aging is also accelerated by corrosion and fouling of the condenser and evaporator tubes. The principal cause of chiller failures is lack of adequate monitoring. Lack of performing scheduled maintenance and human errors also contribute to failures.

Research Organization:
US Nuclear Regulatory Commission (NRC), Washington, DC (United States). Div. of Engineering; Pacific Northwest National Lab. (PNNL), Richland, WA (United States)
Sponsoring Organization:
Nuclear Regulatory Commission, Washington, DC (United States)
DOE Contract Number:
AC06-76RL01830
OSTI ID:
10186028
Report Number(s):
NUREG/CR-6043-Vol.1; PNL-8614-Vol.1; ON: TI94001006; TRN: 93:024032
Resource Relation:
Other Information: PBD: Sep 1993
Country of Publication:
United States
Language:
English

Similar Records

Aging assessment of essential HVAC chillers used in nuclear power plants
Technical Report · Sun Sep 01 00:00:00 EDT 1996 · OSTI ID:10186028

INNOVATIVE HYBRID GAS/ELECTRIC CHILLER COGENERATION
Technical Report · Wed Jun 30 00:00:00 EDT 2004 · OSTI ID:10186028

DOE-defense program`s CFC retrofit plan for HVAC/chillers
Journal Article · Sat Nov 01 00:00:00 EST 1997 · Strategic Planning for Energy and the Environment · OSTI ID:10186028