Title: Evaluation of secondary coolant control design alternatives and their effects on heat removal performance

Technical Report ·
DOI:https://doi.org/10.2172/10140253· OSTI ID:10140253

This report documents a series of calculations that evaluate the performance of the core-inlet temperature controller under different transient conditions and design options. The present analyses show that the core-inlet temperature can be controlled at {approx}45{degrees}C under all transient conditions analyzed using the controller design described in the conceptual design report, which includes variable-speed secondary coolant pumps and variable-speed cooling tower fans. This study also shows that a constant-speed secondary pump would be sufficient to maintain core-inlet temperature <45{degrees}C if this temperature is allowed to drop below the set point during some demanding transients, such as normal startup. The use of secondary loop hot coolant to warm the reactor building was also evaluated; however, optimization of the secondary hot-leg temperature can only be achieved by trading off control of the primary side core-inlet temperature.

Research Organization:
Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC05-84OR21400
OSTI ID:
10140253
Report Number(s):
ORNL/TM-12649; ON: DE94009498; TRN: 94:004506
Resource Relation:
Other Information: PBD: Mar 1994