Purex canyon exhaust fan bearing temperature monitoring system doric 245 datalogger programming
A micro-processor based datalogger is used to monitor, display, and log seventeen RTD temperature channels. Five bearings are monitored for each of the three electric motor-fan assemblies and two bearings are monitored on the steam turbine unit. Several alarms per data channel (a High alarm at 236 degrees and a High High alarm at 246 degrees F) will alert the operation`s staff to increasing abnormal bearing temperatures. This procedure is cross-referenced to the manufacturers manual. All programming steps will have the following footnote: Mpg x-xx. The Mpg refers to the Manual page, with x as the section number and xx as the page number in that section. When more information is needed, such as pictures or details, then the manual section and page number is provided.
- Research Organization:
- Westinghouse Hanford Co., Richland, WA (United States)
- Sponsoring Organization:
- USDOE, Washington, DC (United States)
- DOE Contract Number:
- AC06-87RL10930
- OSTI ID:
- 10108592
- Report Number(s):
- WHC-SD-WM-SDR-008; ON: DE95005469; TRN: 95:001056
- Resource Relation:
- Other Information: PBD: 6 Sep 1994
- Country of Publication:
- United States
- Language:
- English
Similar Records
Vent Stack Liquid N2 RTD Temperature Sensor
Low-level RF LabVIEW{reg_sign} control software user`s manual: Version 1.0
Related Subjects
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
HANFORD RESERVATION
RADIOACTIVE WASTE MANAGEMENT
RADIOACTIVE WASTE STORAGE
MONITORING
EXHAUST SYSTEMS
BEARINGS
TEMPERATURE MEASUREMENT
DATA ACQUISITION SYSTEMS
DATA ACQUISITION
052002
320303
WASTE DISPOSAL AND STORAGE
EQUIPMENT AND PROCESSES