skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Use of treated gasification wastewater in a pilot cooling tower. Phase I. Final report for the period ending January 31, 1984

Technical Report ·
OSTI ID:7182621

During the UNDERC cooling tower tests, data were colleced and evaluated in five major areas: characterization of cooling tower streams, process performance, biofouling, corrosion, and inorganic/organic fouling. A summary of the results and conclusions for each area is presented. Recommendations are provided for research and development programs to further define the pretreatment and operating requirements for the use of wastewater as cooling tower makeup. The results of the Phase I-Pilot Cooling Tower test have revealed several potential problems that may arise from the use of a relatively high organic content gas liquor as cooling tower makeup. Most of the problems identified are related to the presence of organics in the wastewater which promote biofouling/fouling, corrosion, and emissions from the cooling tower. The Phase II-Pilot Cooling Tower Test will address this issue by identifying the advantages of further treatment of stripped gas liquor to reduce the organic content to a lower level before use in the cooling tower. This test will parallel the Phase I test using the same system and monitoring procedures. Comparison of the results of Phase I and Phase II tests will provide an indication of how well problem areas can be avoided with additional makeup water pretreatment. 39 references, 34 tables, and 25 figures.

Research Organization:
North Dakota Univ., Grand Forks (USA). Energy Research Center; Radian Corp., Austin, TX (USA)
DOE Contract Number:
FC21-83FE60181
OSTI ID:
7182621
Report Number(s):
DOE/FE/60181-1602; ON: DE84012119
Resource Relation:
Other Information: Portions are illegible in microfiche products. Original copy available until stock is exhausted
Country of Publication:
United States
Language:
English