Title: Flashback from waste gas incinerator into air supply piping

Journal Article · · Plant/Operations Progress; (United States)
; ;  [1]
  1. Rohm and Haas Texas Inc., Deer Park (United States)

A waste gas incinerator experienced a flashback with a pressure wave in the Suction Vent Gas (SVG) system. Extensive damage resulted to the SVG flame arrestor, SVG fan, SVG valves, and incinerator piping. There were no injuries. The primary cause of the incident is believed to have been a fuel rich SVG stream that was rapidly introduced into the incinerator creating a puff.' This puff' allowed flame from the natural gas ring burner to blow back into the windbox igniting the fuel rich SVG. The combustion of gas in the ducting then created a pressure wave that blew apart the flame arrestor and caused the remainder of the damage.

OSTI ID:
7068939
Journal Information:
Plant/Operations Progress; (United States), Vol. 11:2; ISSN 0278-4513
Country of Publication:
United States
Language:
English