skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Ground-coupled heat pump demonstration

Technical Report ·
OSTI ID:6898238

This report presents the results of a field evaluation of an innovative ground-coupled heat pump system which features a unique collector design and system control strategy aimed at maximizing heat pump performance by minimizing ground temperature change. The collector design includes several short closed loops, each consisting of a pair of polyethylene pipes buried 12 to 18 inches apart in a horizontal trench approximately six feet below ground. A micropressor is used to control flow and optimize system operation. Extrapolation of the results of experiments conducted on a unit length (250 ft.) of collector field during the 1981-82 and 1982-83 heating seasons indicates that a system seasonal performance factor of 2.75 to 3.0 will be achievable in practice.

Research Organization:
Spencertown Geo-Solar Associates, NY (USA)
OSTI ID:
6898238
Report Number(s):
PB-84-156223
Country of Publication:
United States
Language:
English

Similar Records

Ground-coupled heat pump demonstration
Technical Report · Thu Sep 01 00:00:00 EDT 1983 · OSTI ID:6898238

Ground-coupled heat-pump-system experimental results
Conference · Sat Jan 01 00:00:00 EST 1983 · OSTI ID:6898238

Ground-coupled heat pump system experimental results
Conference · Wed Jun 01 00:00:00 EDT 1983 · ASHRAE Trans.; (United States) · OSTI ID:6898238