Ground-coupled heat pump demonstration
This report presents the results of a field evaluation of an innovative ground-coupled heat pump system which features a unique collector design and system control strategy aimed at maximizing heat pump performance by minimizing ground temperature change. The collector design includes several short closed loops, each consisting of a pair of polyethylene pipes buried 12 to 18 inches apart in a horizontal trench approximately six feet below ground. A micropressor is used to control flow and optimize system operation. Extrapolation of the results of experiments conducted on a unit length (250 ft.) of collector field during the 1981-82 and 1982-83 heating seasons indicates that a system seasonal performance factor of 2.75 to 3.0 will be achievable in practice.