Low-Level, Measured Response of Los Alamos National Laboratories TA 16 - Building 411 and TA 8 - Building 23 to Direct Flash Attachment of Lightning
On September 24, 25, 28, and 29, 1998 and on October 19 and 23, 1998, transfer impedance measurements were made on Los Alamos National Laboratories TA 16 - Building 411 and TA 8-- Building 23 to characterize their interior open-circuit voltage response to a direct lightning flash attachment to the structures. The theory, history, measurement methods and equipment, and specific measured results are detailed. The measured results demonstrate that if the remaining metallic penetrations are bonded, then the rebar of the two structures is sufficiently well connected to form a Faraday cage that reduces the maximum open-circuit voltage inside the structure to a sufficiently low level that the required standoff distance to prevent arcing to explosive assemblies is 6.8 inches for TA 16 - Building 411 and is 11.5 inches for TA 8 - Building 23.
- Research Organization:
- Sandia National Laboratories (SNL), Albuquerque, NM, and Livermore, CA (United States)
- Sponsoring Organization:
- USDOE
- DOE Contract Number:
- AC04-94AL85000
- OSTI ID:
- 6383578
- Report Number(s):
- SAND99-0233; ON: DE00008367
- Country of Publication:
- United States
- Language:
- English