skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Synchronized sampling improves fault location

Journal Article · · IEEE Computer Applications in Power
DOI:https://doi.org/10.1109/67.372673· OSTI ID:63026
 [1];  [2]
  1. Texas A and M Univ., College Station, TX (United States)
  2. Lamar Univ., Beaumont, TX (United States)

Transmission line faults must be located accurately to allow maintenance crews to arrive at the scene and repair the faulted section as soon as possible. Rugged terrain and geographical layout cause some sections of power transmission lines to be difficult to reach. In the past, a variety of fault location algorithms were introduced as either an add-on feature in protective relays or stand-alone implementation in fault locators. In both cases, the measurements of current and voltages were taken at one terminal of a transmission line only. Under such conditions, it may become difficult to determine the fault location accurately, since data from other transmission line ends are required for more precise computations. In the absence of data from the other end, existing algorithms have accuracy problems under several circumstances, such as varying switching and loading conditions, fault infeed from the other end, and random value of fault resistance. Most of the one-end algorithms were based on estimation of voltage and current phasors. The need to estimate phasors introduces additional difficulty in high-speed tripping situations where the algorithms may not be fast enough in determining fault location accurately before the current signals disappear due to the relay operation and breaker opening. This article introduces a unique concept of high-speed fault location that can be implemented either as a simple add-on to the digital fault recorders (DFRs) or as a stand-alone new relaying function. This advanced concept is based on the use of voltage and current samples that are synchronously taken at both ends of a transmission line. This sampling technique can be made readily available in some new DFR designs incorporating receivers for accurate sampling clock synchronization using the satellite Global Positioning System (GPS).

OSTI ID:
63026
Journal Information:
IEEE Computer Applications in Power, Vol. 8, Issue 2; Other Information: PBD: Apr 1995
Country of Publication:
United States
Language:
English

Similar Records

Use of Machine Learning on PMU Data for Transmission System Fault Analysis
Conference · Sun Aug 28 00:00:00 EDT 2022 · OSTI ID:63026

Fault location using digital relay data
Journal Article · Sat Jul 01 00:00:00 EDT 1995 · IEEE Computer Applications in Power · OSTI ID:63026

An accurate fault locator with compensation for apparent reactance in the fault resistance resulting from remote-end infeed
Journal Article · Fri Feb 01 00:00:00 EST 1985 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:63026