230 kV operation of a substation designed for 115 kV by controlling voltage transients
Journal Article
·
· IEEE Trans. Power Appar. Syst.; (United States)
Arresters applied at the terminals of gas insulated substations have been used successfully for protection from switching and lightning surges. This arrester application for gas insulated substations permits the use of lower insulation levels and therefore more economical substations. In principle, the same technique can be applied to air insulated substations. This paper describes the analysis of transient voltages in a substation designed for 115 kV which is scheduled for operation at 230 kV. Both arrester rating and location are considered in this analysis. It is shown that complete substation protection is possible by addition of both arresters and capacitors.
- OSTI ID:
- 6265819
- Journal Information:
- IEEE Trans. Power Appar. Syst.; (United States), Vol. PAS-103:9
- Country of Publication:
- United States
- Language:
- English
Similar Records
Study to determine the basic insulation level requirements for a prototype 1200 kV CGIT cable system
Lightning overvoltage protection of the paddock 362-145 kV Gas-Insulated Substation
Lightning protection requirements of SF/sub 6/ substation determined by hybrid simulator. [115/345 kv station]
Technical Report
·
Sun Jul 01 00:00:00 EDT 1979
·
OSTI ID:6265819
Lightning overvoltage protection of the paddock 362-145 kV Gas-Insulated Substation
Journal Article
·
Mon Jan 01 00:00:00 EST 1990
· IEEE (Institute of Electrical and Electronics Engineers) Transactions on Power Delivery; (USA)
·
OSTI ID:6265819
+1 more
Lightning protection requirements of SF/sub 6/ substation determined by hybrid simulator. [115/345 kv station]
Conference
·
Sat Jan 01 00:00:00 EST 1977
· Proc. Am. Power Conf.; (United States)
·
OSTI ID:6265819
+1 more
Related Subjects
24 POWER TRANSMISSION AND DISTRIBUTION
GAS-INSULATED SUBSTATIONS
EQUIPMENT PROTECTION DEVICES
LIGHTNING ARRESTERS
LOAD ANALYSIS
CAPACITORS
CONTROL
COST BENEFIT ANALYSIS
ELECTRIC POTENTIAL
ELECTRICAL TRANSIENTS
KEV RANGE 100-1000
ELECTRICAL EQUIPMENT
ENERGY RANGE
EQUIPMENT
KEV RANGE
POWER SUBSTATIONS
TRANSIENTS
VOLTAGE DROP
200300* - Electric Power Engineering- Power Transmission & Distribution- (-1989)
GAS-INSULATED SUBSTATIONS
EQUIPMENT PROTECTION DEVICES
LIGHTNING ARRESTERS
LOAD ANALYSIS
CAPACITORS
CONTROL
COST BENEFIT ANALYSIS
ELECTRIC POTENTIAL
ELECTRICAL TRANSIENTS
KEV RANGE 100-1000
ELECTRICAL EQUIPMENT
ENERGY RANGE
EQUIPMENT
KEV RANGE
POWER SUBSTATIONS
TRANSIENTS
VOLTAGE DROP
200300* - Electric Power Engineering- Power Transmission & Distribution- (-1989)