skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: The AC clean-fog test for contaminated insulators

Journal Article · · IEEE Trans. Power Appar. Syst.; (United States)
OSTI ID:6139186

The paper summarizes the results of clean-fog tests conducted by eleven task force laboratories on a common suspension insulator, IEEE insulator. The test series done according to a specific set of guidelines, show considerable dispersion in the fifty per cent flashover voltage between the laboratories. The significant parameters of the clean-fog method that influence the fifty per cent flashover voltage are discussed. More controls in testing are needed before the formalization of the clean-fog method as a standard contamination test for high voltage ac insulators can be made.

OSTI ID:
6139186
Journal Information:
IEEE Trans. Power Appar. Syst.; (United States), Vol. 102:3
Country of Publication:
United States
Language:
English