Application of system identification techniques to an rf cavity tuning loop
Conference
·
OSTI ID:5731624
- Superconducting Super Collider Lab., Dallas, TX (USA)
- Rutherford Appleton Lab., Chilton (UK)
Modern system identification is applied to rf cavity tuning on the ISIS synchrotron. Four types of test signals are investigated to assess their suitability for real time measurement in an accelerator environment. The Pseudo Random Binary Signal (PRBS) appears to be the most advantageous. Measurements under normal operating conditions allow automatic identification for a self-adapting loop. The interactive software MATLAB is used to process the data and the identified model is represented in pole-zero form. The model shows good correlation with system performance. 6 refs., 7 figs.
- Research Organization:
- Superconducting Super Collider Lab., Dallas, TX (United States)
- Sponsoring Organization:
- USDOE; USDOE, Washington, DC (USA)
- DOE Contract Number:
- AC02-89ER40486
- OSTI ID:
- 5731624
- Report Number(s):
- SSCL-307; CONF-900603-62; ON: DE91015280; TRN: 91-021657
- Resource Relation:
- Conference: EPAC '90: 2nd European particle accelerator conference ACROPOLIS, Nice (France), 11-16 Jun 1990
- Country of Publication:
- United States
- Language:
- English
Similar Records
Advanced System Identification Techniques for Wind Turbine Structures with Special Emphasis on Modal Parameters
Sliding mode controller of rf cavity tuning loop
Design of a Linear-Quadratic-Gaussian Controller for a Single-Cavity Rigid-Bunch RF-System
Technical Report
·
Thu Jun 01 00:00:00 EDT 1995
·
OSTI ID:5731624
Sliding mode controller of rf cavity tuning loop
Conference
·
Wed May 01 00:00:00 EDT 1991
·
OSTI ID:5731624
Design of a Linear-Quadratic-Gaussian Controller for a Single-Cavity Rigid-Bunch RF-System
Technical Report
·
Mon Jan 26 00:00:00 EST 2009
·
OSTI ID:5731624