This report summarizes findings of a fire protection review conducted February 19, 1986 at the Western Area Power Administration's Miles City Converter Station. This facility would not be considered a Highly Protected Risk. Major physical deficiencies include lack of automatic sprinkler protection, an inadequate water supply, and an inadequate fire wall around the Valve Hall. Major human element deficiencies include delayed response to site alarms and the lack of monthly inspection programs. The loss potential is $23,000,000. This is made up of $15,000,000 property damage and $8,000,000 loss of income for an expected 18 month outrage.
- Research Organization:
- Factory Mutual Research Corp., Norwood, MA (USA)
- DOE Contract Number:
- AC01-84PE17056
- OSTI ID:
- 5467179
- Report Number(s):
- DOE/PE/17056-T12; ON: TI86026857
- Country of Publication:
- United States
- Language:
- English
Similar Records
Fire protection review: revisit No. 2, Fermi National Accelerator Laboratory, Batavia, Illinois
Audit Report, "Fire Protection Deficiencies at Los Alamos National Laboratory"
Fire protection review revisit No. 2, Argonne National Laboratory, Argonne, Illinois
Technical Report
·
Sat Mar 01 00:00:00 EST 1986
·
OSTI ID:5467179
Audit Report, "Fire Protection Deficiencies at Los Alamos National Laboratory"
Technical Report
·
Mon Jun 01 00:00:00 EDT 2009
·
OSTI ID:5467179
Fire protection review revisit No. 2, Argonne National Laboratory, Argonne, Illinois
Technical Report
·
Wed May 01 00:00:00 EDT 1985
·
OSTI ID:5467179