skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Modern excitation system models and verification tests

Conference · · Proc. Am. Power Conf.; (United States)
OSTI ID:5279648

Excitation systems have been supplied on turbine-generators with response ratios from 0.5 to 3.5, some with high initial response voltage characteristics. Tests on brushless excitation systems have shown that the new model features for alternator-rectifier excitation systems described in this paper provide a good representation of the actual response. Such tests, along with an examination of the new model structures, are presented in this paper. 4 refs.

Research Organization:
Westinghouse Electr Corp, East Pittsburgh, Pa
OSTI ID:
5279648
Report Number(s):
CONF-800424-
Journal Information:
Proc. Am. Power Conf.; (United States), Vol. 42; Conference: American power conference, Chicago, IL, USA, 21 Apr 1980
Country of Publication:
United States
Language:
English