Title: Analysis of the harmonic distortion resulting from the interaction between synchronous machines and HVDC convertors

Conference ·
OSTI ID:5045447

The harmonic voltage distortion caused by static convertors can be greatly affected by the presence of local salient-pole synchronous generators or compensators. Such machines act as harmonic converters and are sensitive to the sequence of the fundamental and harmonic frequencies. This paper provides an accurate equivalent circuit for the synchronous machine in the multi-harmonic space, integrates such model with other a.c. system components and describes an iterative sequential algorithm to derive the harmonic interaction between the synchronous machine and static convertor.

Research Organization:
Univ. of Canterbury, Christchurch
OSTI ID:
5045447
Report Number(s):
CONF-860705-
Resource Relation:
Conference: IEEE Power Engineering Society summer meeting, Mexico City, Mexico, 20 Jul 1986
Country of Publication:
United States
Language:
English