skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Pollution performance of 110 kV metal oxide arresters

Abstract

Pollution test results of single unit 110 kV metal oxide surge arresters with porcelain housing according to the solid layer and salt fog methods are presented. During 6 hours of testing, the internal and external charge and maximum temperature along the varistor column were measured. The formation of single stable dry bands on the housing was often observed, especially during salt fog tests. In such cases, the varistor temperature can reach about 70 C. The simple electrical model of the arrester enabling calculations of voltages and currents as a function of arrester and pollution parameters is shown.

Authors:
;  [1];  [2];  [3]
  1. Technical Univ. of Wroclaw (Poland). Dept. of Electrical Engineering
  2. Mississippi State Univ., MS (United States). Dept. of Electrical and Computer Engineering
  3. Univ. of Stuttgart (Germany). Dept. of Electrical Engineering
Publication Date:
OSTI Identifier:
492190
Report Number(s):
CONF-960725-
Journal ID: ITPDE5; ISSN 0885-8977; TRN: IM9730%%69
Resource Type:
Journal Article
Journal Name:
IEEE Transactions on Power Delivery
Additional Journal Information:
Journal Volume: 12; Journal Issue: 2; Conference: 1996 Summer meeting of the IEEE Power Engineering Society, Denver, CO (United States), 28 Jul - 1 Aug 1996; Other Information: PBD: Apr 1997
Country of Publication:
United States
Language:
English
Subject:
24 POWER TRANSMISSION AND DISTRIBUTION; VOLTAGE REGULATORS; PERFORMANCE TESTING; HVAC SYSTEMS; SURFACE CONTAMINATION; FOG; SALTS

Citation Formats

Chrzan, K, Pohl, Z, Grzybowski, S, and Koehler, W. Pollution performance of 110 kV metal oxide arresters. United States: N. p., 1997. Web. doi:10.1109/61.584358.
Chrzan, K, Pohl, Z, Grzybowski, S, & Koehler, W. Pollution performance of 110 kV metal oxide arresters. United States. https://doi.org/10.1109/61.584358
Chrzan, K, Pohl, Z, Grzybowski, S, and Koehler, W. 1997. "Pollution performance of 110 kV metal oxide arresters". United States. https://doi.org/10.1109/61.584358.
@article{osti_492190,
title = {Pollution performance of 110 kV metal oxide arresters},
author = {Chrzan, K and Pohl, Z and Grzybowski, S and Koehler, W},
abstractNote = {Pollution test results of single unit 110 kV metal oxide surge arresters with porcelain housing according to the solid layer and salt fog methods are presented. During 6 hours of testing, the internal and external charge and maximum temperature along the varistor column were measured. The formation of single stable dry bands on the housing was often observed, especially during salt fog tests. In such cases, the varistor temperature can reach about 70 C. The simple electrical model of the arrester enabling calculations of voltages and currents as a function of arrester and pollution parameters is shown.},
doi = {10.1109/61.584358},
url = {https://www.osti.gov/biblio/492190}, journal = {IEEE Transactions on Power Delivery},
number = 2,
volume = 12,
place = {United States},
year = {Tue Apr 01 00:00:00 EST 1997},