Title: Energy savings from repair of uncontrolled airflow in 18 small commercial buildings

Conference ·
OSTI ID:433759
; ; ;  [1];  [2]
  1. Florida Solar Energy Center, Cocoa, FL (United States)
  2. Building Science Corp., Chestnut Hill, MA (United States)

Uncontrolled airflow, including duct leakage, pressure imbalances caused by closed interior doors, and exhaust/intake airflow imbalance, was characterized in 70 commercial buildings. In 18 of these buildings, uncontrolled airflows were repaired and energy savings from these repairs were monitored. In most buildings, the retrofit was duct repair. In other cases, outdoor airflow was reduced and return air transfers were provided. Cooling energy use was reduced by an average 15.1% in these 18 buildings. With an average repair cost of $455 and average cooling energy savings of $195 per year, uncontrolled airflow retrofits proved to be very cost-effective. Various factors indicate that greater energy savings could be achieved in the future.

OSTI ID:
433759
Report Number(s):
CONF-960606-; TRN: IM9709%%193
Resource Relation:
Conference: 1996 annual meeting of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), Inc., San Antonio, TX (United States), 22-26 Jun 1996; Other Information: PBD: 1996; Related Information: Is Part Of ASHRAE transactions 1996: Volume 102, Part 2; PB: 836 p.
Country of Publication:
United States
Language:
English