Title: An innovative technology for indoor environmental monitoring

Conference ·
OSTI ID:351002
;  [1]
  1. Omega, Itasca, IL (United States)

This paper presents the results of two field studies for an indoor air quality (IAQ) monitoring system, utilizing Echelon{reg_sign} technology to eliminate the need for direct wiring of remote sensing units to a central datalogger. Up to eight sensors of differing technology and up to 256 remote units can feed one datalogger. The results can then be analyzed and displayed in various formats (i.e., tables, graphs, and reports) or used as input to HVAC and other control devices. The system was installed and collected data during a summer test period in a commercial building and a winter test period in an industrial facility. These sites were chosen because results of previous IAQ assessments showed elevated CO levels. The commercial building is a municipal facility that houses public works maintenance and engineering functions. The industrial location is a manufacturer of machined metal parts and shares shipping and receiving docks with an adjacent foundry and casting operation. The system used in these field tests consisted of three remote sensing units, which were plugged directly into standard electrical outlets in various places throughout the sites, and one central datalogger which polled the remote units and collected the data. The remote units, as configured for these field tests, continuously measured methane, carbon monoxide (CO), relative humidity (RH), and temperature (T). Other sensors, including carbon dioxide (CO{sub 2}) and specialty gases, can be utilized. In both tests, the data were collected over a period of several weeks. The data collected showed quick detection and sensor recovery of CO spikes and accurate tracking of T and RH variations. No methane was detected during the field tests. The field tests showed the viability of this system to monitor IAQ parameters for the purpose of alarm and control functions.

OSTI ID:
351002
Report Number(s):
CONF-970677-; TRN: IM9925%%164
Resource Relation:
Conference: 90. annual meeting and exhibition of the Air and Waste Management Association, Toronto (Canada), 8-13 Jun 1997; Other Information: PBD: 1997; Related Information: Is Part Of 1997 proceedings of the Air and Waste Management Association`s 90. annual meeting and exhibition; PB: [7000] p.
Country of Publication:
United States
Language:
English