Title: A liquid overfeeding military air conditioner with a quench valve

Conference ·
OSTI ID:345216
;  [1];  [2]
  1. Oak Ridge National Lab., TN (United States)
  2. Army CECOM RD and E Center, Fort Belvoir, VA (United States)

A 3.3-ton rated military air-conditioning unit has been studied experimentally for baseline and liquid overfeeding (LOF) operation. The tests before any modification, using the nameplate-specified refrigerant charge, showed the measured cooling capacity to be less than 1% off the rated capacity at 95 F (35 C) ambient temperature. The test results, after modification, indicate that LOF operation outperforms the baseline case over a wide ambient temperature range in terms of cooling capacity, power consumption, and system coefficient of performance (COP). At a 95 F (35 C) test point, LOF operation has a cooling capacity of 51,100 Btu per hour, which is an 18% improvement over the baseline operation capacity of 42,500 Btu per hour. The COP for LOF at 95 F (35 C) is 2.62, which is 29% better than the baseline COP of 2.03. However, an optimal refrigerant charge is essential for LOF to work properly.

Sponsoring Organization:
Department of the Army, Washington, DC (United States); USDOE, Washington, DC (United States)
DOE Contract Number:
AC05-84OR21400
OSTI ID:
345216
Report Number(s):
CONF-9702141-; TRN: IM9922%%149
Resource Relation:
Conference: American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) winter meeting, Philadelphia, PA (United States), 24-28 Feb 1997; Other Information: PBD: 1997; Related Information: Is Part Of ASHRAE transactions: Technical and symposium papers, 1997. Volume 103, Part 1; PB: 1136 p.
Country of Publication:
United States
Language:
English