Title: Reentry of radon from mitigation system outlets

Conference ·
OSTI ID:33279
;  [1]
  1. Pennsylvania State Univ., University Park, PA (United States). Dept. of Architectural Engineering

Some radon mitigation systems draw air with a high radon concentration from under the basement floors of houses and exhaust it outdoors. The objective of this project was to measure the reentry rates of radon released at roof level and at ground level near a house to determine whether exhaust above the roof is necessary. This was done by using a portable mockup of a radon mitigation system exhaust, with sulfur hexafluoride (SF{sub 6}) as a tracer gas. The roof-level exhaust produced maximum indoor sulfur hexafluoride concentrations that were significantly lower than those from the ground-level exhaust. This suggests that the better radon discharge location is on the roof of a house.

OSTI ID:
33279
Report Number(s):
CONF-9406105-; TRN: 95:009081
Resource Relation:
Conference: 1994 American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) annual meeting, Orlando, FL (United States), 25-29 Jun 1994; Other Information: PBD: 1994; Related Information: Is Part Of ASHRAE transactions 1994: Technical and symposium papers. Volume 100, Part 2; PB: 1372 p.