The issue of sound quality in offices and other occupied spaces has been of continuing interest since the 1950s. Existing assessment methods do not adequately account for the low-frequency background sound (< 250 Hz) produced by operating heating, ventilating, and air-conditioning (HVAC) systems, in particular, low-frequency rumble. This paper discusses the results of ASHRAE-sponsored research in which more than 75 HVAC noise samples were collected, normalized, and categorized in terms of sound quality. The results support previous findings that a neutral curve has a slope of approximately {minus}5 decibels (dB) per octave. There is also support for the contention that the balanced noise criterion B (NCB) curves are overly conservative in the region from 63 to 500 Hz and overly permissive below 63 Hz when compared with the room criteria (RC) curves. A modified set of room sound quality (RSQ) curves -- the room sound quality (RSQ) curves -- is proposed.

OSTI ID:
33262
Report Number(s):
CONF-9406105-; TRN: IM9518%%83
Resource Relation:
Conference: 1994 American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) annual meeting, Orlando, FL (United States), 25-29 Jun 1994; Other Information: PBD: 1994; Related Information: Is Part Of ASHRAE transactions 1994: Technical and symposium papers. Volume 100, Part 2; PB: 1372 p.
Country of Publication:
United States
Language:
English