Title: Study on detection for the defects of XLPE cable lines

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.489320· OSTI ID:244798
; ;  [1]; ;  [2]; ;  [3]
  1. Chubu Electric Power Co., Inc., Nagoya (Japan)
  2. Furukwa Electric Co., Ltd., Tokyo (Japan)
  3. Sumitomo Electric Industries, Ltd., Osaka (Japan)

This paper is a report on the results of a basic study of testing methods to replace the dc after laying test that is presently most frequently used as an after laying test for XLPE cable lines. Chosen as the alternative waveforms for dc voltage were damped oscillating wave (OSW) and very-low-frequency wave (VLF) voltage. Experiments were conducted on the ability to detect various types of line defects under these voltages. It was found that these alternative waveforms are promising as after laying test voltage waveforms to replace dc and that greater defect detection ability can be achieved by combining them when conducting tests.

OSTI ID:
244798
Report Number(s):
CONF-950727-; ISSN 0885-8977; TRN: IM9627%%120
Journal Information:
IEEE Transactions on Power Delivery, Vol. 11, Issue 2; Conference: 1995 IEEE Power Engineering Society summer meeting, Portland, OR (United States), 23-27 Jul 1995; Other Information: PBD: Apr 1996
Country of Publication:
United States
Language:
English

Similar Records

Application of advanced after-laying test to long-distance 275 kV XLPE cable lines
Journal Article · Sat Apr 01 00:00:00 EST 1995 · IEEE Transactions on Power Delivery · OSTI ID:244798

Online Monitoring of Medium Voltage Cable Systems with Spread Spectrum Time Domain and Frequency Domain Reflectometry
Technical Report · Fri Sep 29 00:00:00 EDT 2023 · OSTI ID:244798

High voltage VLF testing of power cables
Journal Article · Tue Apr 01 00:00:00 EST 1997 · IEEE Transactions on Power Delivery · OSTI ID:244798