Airflow studies in a forced ventilated chamber with low partitions
- Hong Kong Polytechnic Univ. (Hong Kong). Dept. of Building Services Engineering
A climate chamber was used to study experimentally the airflow characteristics in a ventilated space with low partitions. Two types of commonly used air distribution devices were selected for the study--a ceiling diffuser and side grille systems. A total of 16 tests were performed using the two diffusers with partition heights varying up to 1.8 m (5.91 ft) above floor level. From the measured results, the thermal comfort indices were assessed. A stabilization effect of airflow was found when the partition height reached 1.8 m (5.91 ft). Local draft risk was located in the occupied zone. Also, the modified Archimedes number proposed by Jackman (1990) was used to describe the indoor airflow in the absence of a workable design guide for partitioned spaces.
- OSTI ID:
- 211794
- Report Number(s):
- CONF-950624-; TRN: IM9617%%110
- Resource Relation:
- Conference: Annual meeting of the American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc. (ASHRAE), San Diego, CA (United States), 24-28 Jun 1995; Other Information: PBD: 1995; Related Information: Is Part Of ASHRAE transactions 1995: Technical and symposium papers. Volume 101, Part 2; PB: 1497 p.