skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Protocol for field testing of tall buildings to determine envelope air leakage rate

Conference ·
OSTI ID:20085600

The objective of this project was to develop a relatively simple, accurate method for testing the overall envelope leakage rate of tall buildings. Two fan pressurization test techniques, the floor-by-floor blower door method and the air-handler method, were developed and tested on two buildings. Criteria for conducting accurate tests were developed, including limitations on outdoor air temperature and wind speed. The floor-by-floor blower door method permits isolation and measurement of the leakage flow rate of a single floor, but it is difficult and time-consuming to apply. The air-handler method uses building air distribution fans for pressurization. It is most easily applied on a system-by-system level rather than floor-by-floor. fan airflow techniques including orifice plate, pitot traverse, and tracer gas dilution were considered. The tracer gas method was found to be relatively easy to apply and highly accurate. Fan airflow rate measurement uncertainty by tracer gas was estimated to be 5.4% to 8.8% for the cases considered, assuming a 5% uncertainty in interzonal leakage.

Research Organization:
Pennsylvania State Univ., University Park, PA (US)
OSTI ID:
20085600
Resource Relation:
Conference: ASHRAE Annual Meeting, Seattle, WA (US), 06/18/1999--06/23/1999; Other Information: PBD: 1999; Related Information: In: ASHRAE Transactions: Technical and symposium papers presented at the 1999 annual meeting in Seattle, Washington of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.; Volume 105, Part 2, by Geshwiler, M.; Harrell, D.; Roberson, T. [eds.], 1360 pages.
Country of Publication:
United States
Language:
English

Similar Records

Measured airflows in a multifamily building
Journal Article · Fri Sep 01 00:00:00 EDT 1995 · American Society for Testing and Materials, Special Technical Publication · OSTI ID:20085600

Reducing Uncertainty for the DeltaQ Duct Leakage Test
Conference · Sat May 01 00:00:00 EDT 2004 · OSTI ID:20085600

Analysis of errors for a fan-pressurization technique for measuring inter-zonal air leakage
Conference · Thu Sep 01 00:00:00 EDT 1988 · OSTI ID:20085600