Title: Automated fault detection and diagnostics for outdoor-air ventilation systems and economizers: Methodology and results from field testing

Conference ·
OSTI ID:20002337

This paper describes a prototype diagnostic system that automatically detects and diagnoses problems with outdoor-air ventilation and economizer operation in commercial buildings using data available from building automation systems (BASs). The system also provides context-sensitive suggestions for correcting the problems detected. The diagnostics are based on rules derived from engineering models of proper and improper air-handler performance. These rules are implemented as a decision tree structure in software. Data collected periodically from a BAS are used to navigate the decision tree and reach conclusions regarding the operating state of the air-handling unit (AHU). Errors and uncertainty in measured data are handled through adjustable tolerance settings in the diagnostic software. Results to date indicate that meaningful results can be obtained using this approach. The diagnostic system can be implemented for either continuous or batch processing of data. This system is currently installed on seven AHUs in two buildings. Four of the seven AHUs were found to have problems shortly after installation of the diagnostic system. The diagnostic methodology, its implementation in software, the field installations, and test results are described in this paper. The findings clearly demonstrate the potential for automated diagnostic technology to serve an important role in commercial building commissioning and operation.

Research Organization:
Pacific Northwest National Lab., Richland, WA (US)
Sponsoring Organization:
USDOE
DOE Contract Number:
AC06-76RL01830
OSTI ID:
20002337
Report Number(s):
CONF-990102-; ISSN 0001-2505; TRN: IM200002%%337
Resource Relation:
Conference: ASHRAE Winter Meeting, Chicago, IL (US), 01/23/1999--01/27/1999; Other Information: PBD: 1999; Related Information: In: ASHRAE transactions 1999: Technical and symposium papers. Volume 105, Part 1, 1387 pages.
Country of Publication:
United States
Language:
English

Similar Records

Building Diagnostic Market Deployment - Final Report
Technical Report · Mon Apr 30 00:00:00 EDT 2012 · OSTI ID:20002337

Voltron Compatible Whole Building Root-Fault Detection and Diagnosis
Technical Report · Sat Dec 01 00:00:00 EST 2018 · OSTI ID:20002337

Automated Proactive Techniques for Commissioning Air-Handling Units
Journal Article · Sat Aug 30 00:00:00 EDT 2003 · Journal of Solar Energy Engineering--Transactions of the ASME, 125(3):282-291 · OSTI ID:20002337